Number of auxiliary contacts as normally open contact
|
0
|
|---|---|
|
Number of auxiliary contacts as normally closed contact
|
0
|
|
Conditioned rated short-circuit current Iq
|
30 kA
|
|
Rated permanent current Iu
|
80 A
|
|
Rated operation power at AC-23, 400 V
|
37 kw
|
|
Max. rated operation voltage Ue AC
|
690 V
|
|
Rated operation power at AC-3, 400 V
|
30 kw
|
|
Rated short-time withstand current lcw
|
2500 kA
|
|
Rated frequency
|
60 Hz
|
|
Switch size
|
80 A
|
|
Lost power per pole
|
3.6 W
|
|
Conventional free air thermal current (Ith)
|
100 A per IEC
|
|
Conventional enclosed thermal current (Ie)
|
80 A per IEC
|
|
Rated operational voltage (Ue)
|
690V per IEC
|
|
Rated isolation voltage (Ui)
|
690V per IEC
|
|
Continuous current
|
UL/CSA (applications): 80 A
|
|
Rated breaking capacity
|
AC-23A (cosφ 0.45): 800A @ 400V
|
|
Motor FLA rating
|
UL/CSA application: 68A @ 240V, 60 Hz, 3 pole, 3 phase
|
|
Hp motor rating
|
UL/CSA application: 50Hp @ 600V, 60 Hz, 3 pole, 3 phase
|
|
Fuse rating of circuit (type g, G), max
|
Short circuit current (co-ordination type 2): 80A @ 400/415V
|
|
Rated current (Ie)
|
DC-21A (for resistive loads): 80A @ 96V, 2 pole in series, T ≤1 ms, Ue max = 660V
|
|
Rated power (Pe)
|
AC-3: 30 kW @ 690V
|
|
Number of switches
|
1
|
|
Motor drive integrated
|
False
|
|
Voltage release optional
|
False
|
|
Type of electrical connection of main circuit
|
Screw connection
|
|
Switching rate
|
120 ops/h
|
|
Rated impulse voltage (Uimp)
|
8 kV per UL, CSA
|
|
Test voltage (Ui)
|
2.5kV @ 1min
|
|
Version as emergency stop installation
|
False
|
|
Degree of protection (NEMA)
|
Other
|
|
Tightening torque
|
5.6 Nm (50 in-lb)
|
|
Switch configuration
|
OFF-ON 90°
|
|
Rigid wire gauge
|
4...50 mm2 (10...1 AWG)
|
|
Fine strands wire gauge
|
4...35 mm2 (10...1 AWG)
|
|
Knockouts
|
PG-type cable gland entry
|
|
Wire gauge, max
|
Terminal size per IEC 947-1: A9
|
|
Protection class according to IEC 529
|
Switch bodies: IP20 @ motor rating 60 Hz
|
|
Actuator type
|
Select actuator separately
|
|
Version as reversing switch
|
False
|
|
Version as main switch
|
True
|
|
Version as maintenance-/service switch
|
True
|
|
Ambient enclosed temperature
|
-20 °C
|
|
Ambient storage temperature
|
-40 °C
|
|
Ambient operation temperature
|
-25 °C
|